Sensor line surge arrestor packages protect sensor signal lines and dedicated or switched telephone lines. Each signal line uses a two-stage transient suppressor. In the event of a surge, a Zener diode clamps the voltage (24 VDC) to a safe level, while series resistors absorb the remainder. If the voltage is greater than 150 Vac, a gas discharge tube is activated. These components absorb most of the transient and discharge it to ground. After the transient passes, the entire circuit recovers automatically.
Screw terminals are provided for input and output connections. The surge protectors must be mounted in a weatherproof housing.
- 350-B380-24V protects four lines
- 350-B480-24V protects eight lines
NovaLynx offers customized packaged units consisting of a junction box, surge board, ac protection, fused 115 Vac input/output circuits, ground rod, and ground cable. Consult the factory for a quotation.
Specifications
|
Max. DC operating voltage
|
Uc | 28 Vdc |
|
Max. frequency
|
f max. | > 3 MHz |
|
Insertion loss
|
< 1 dB | |
|
Protection mode(s)
|
Common/Differential mode | |
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, X-X (Line/Line)
|
Up | 40 V |
|
Protection level
C3 (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
|
Up | 20 V |
|
DATA SPD TYPE
|
UL497B LISTED | |
|
VOLTS
|
(V) | 24 |
|
WIRES
|
4W+GROUND or 8W+ GROUND | |
|
LINE CURRENT MAX
|
(A) | 0.3 |
|
AMBIENT MIN
|
(C) | -50 |
|
AMBIENT MAX
|
(C) | +85 |
|
RESIDUAL VOLTAGE
|
(V) | 20 |
|
MCOV
|
(V) | 28/ |
|
IN
10 impulses 8/20µs
|
(kA) | 5 |
|
IMAX
8/20µs
|
(kA) | 20 |
|
Iimp
10/350µs
|
(kA) | 5 |
|
DATA SPEED
|
(Mbps) | up to 10MHz |